Product Image

DVS+ Voice Evacuation Control Panel

DVS+ panels include all of the functionality and features required to provide a complete notification and emergency response system. Designed to provide life safety during a fire emergency, DVS+ performs equally well for notification and control of other emergency and non-emergency conditions. Using a modular design DVS+ panels can be configured to meet the specific needs of an installation. Modularity allows modification and expansion to suit changing needs

  • Online Certifications Directory
  • Online Certifications Directory

  • 50 To 200 Watts audio power
  • Up to 20 supervised speaker loops
  • Class A or B wiring, field selectable
  • 25 or 70.7 Vrms, field selectable
  • 8 selectable alarm tones
  • Up to 14 pre-recorded messages, 30 sec. each
  • Dual channel capability
  • Remote microphone option
  • Amplifier back-up option
  • Integral auxiliary audio input
  • Intelligent amplifier overload protection
  • Modular design flexibility
Frequency Response 600 Hz to 3600 Hz
Audio Output Voltage 25 Vrms, field selectable
Speaker Circuits Maximum 25 Watt audio load per amplifier output.
Maximum 15 Watt audio load per zoned speaker loop.
Class A or Class B wiring, field selectable
Power Limited, 18 AWG minimum wire size
10K, 1 Watt end of line resistor
Activation Inputs Polarity Reversing (NAC) 10-30VDC, 10Ma max.
NAC 5A @ 30 VDC
Dry Contact input maximum 2mA operating current
Auxiliary Audio Input: 1 Vrms typical audio input level
10K ohm input impedance
Remote Microphone: 1 Vrms supervised audio input level
24 VDC power limited
Supervised 4 Conductor Cabeling
31"H x 24" W x 4.75" D
Listings/Approvals: UL, CSFM

The DVS+ can provide between 50 and 200 Watts of audio power, field selectable for 25/70.7Vrms operation. Automatic amplifier backup can protect any installed amplifier. Audio output power can be distributed over as many as 20 supervised speaker circuits, field programmed for Class A (Style Z) or Class B (Style Y) wiring. Each amplifier incorporates SigCom’s Intelligent Overload Protection to avoid panel damage without disconnecting the load and disabling the system.

A supervised reverse polarity circuit (NAC), dry contact input or a serial interface can provide the means for DVS+ activation and control. Alarm signals can be automatically or manually directed to selected speaker circuits or to all circuits simultaneously. Eight selectable tones and 2 standard voice messages can be field configured for type, sequence and duration. A total of 14 messages of 30 second duration can be pre-recorded when the DVS-DM8 board is used. Facilities are provided for dual simultaneous messaging. An integral, supervised (Push-To-Talk) microphone is supplied, with the capability for an optional supervised remote microphone. The DVS+ will accept an auxiliary audio input from a telephone page system or similar source.

Every DVS+ panel is pre-engineered, pre-assembled and fully tested.



Product Quick Finder

Find Your Local Sales Rep


For information about International Sales please email your requirement(s) / application(s) to us. We will then contact you by e-mail or phone, with any information that you have requested.